JMF Server Room

Updated: 2026-09-29

Source: JMF Server Room 20260929.drawio.pdf and Watts 1.pdf, live UPS/PDU loads over SNMP

1234567891011121314151617181920212223242526HP Switch, 192.168.0.210, D11HP Switch | 192.168.0.210 | D11HP Switch, 192.168.0.212, D15HP Switch | 192.168.0.212 | D15JMFPMX02, 192.168.3.232, D24, C21JMFPMX02192.168.3.232 | D24, C21Fiber / Comcast, D1, D14Fiber / Comcast | D1, D14Firewall, 192.168.0.194, D23, C9Firewall | 192.168.0.194 | D23, C9Mini NG Switch, D12Mini NG Switch | D12F FW, 192.168.0.190, D6F FW | 192.168.0.190 | D6JMFPMX03, 192.168.3.199, D19, C24JMFPMX03192.168.3.199 | D19, C24JMFPMX04, 192.168.0.232, A14, C16JMFPMX04192.168.0.232 | A14, C16JMFPMX06, 192.168.3.200, A19, C2JMFPMX06192.168.3.200 | A19, C2JMFPMX05, 192.168.3.190, C5, A16JMFPMX05192.168.3.190 | C5, A16Syn NAS, 192.168.0.196, C10, D7Syn NAS192.168.0.196 | C10, D7SRT2200, 192.168.3.250SRT2200192.168.3.250Symmetra RM 6000, 192.168.0.248Symmetra RM 6000192.168.0.248
Rack 1
1234567891011121314151617HP Switch, 192.168.0.211, C20HP Switch | 192.168.0.211 | C20R520 VM, 192.168.3.196, B7, A24R520 VM192.168.3.196 | B7, A24R520 VM, 192.168.0.222, D17, C19R520 VM192.168.0.222 | D17, C19Storage, 192.168.0.220, A8, B10Storage192.168.0.220 | A8, B10R710 VM, 192.168.0.227, A18, C11R710 VM192.168.0.227 | A18, C11SRT2200, 192.168.3.251SRT2200192.168.3.251Symmetra RM 6000, 192.168.0.239Symmetra RM 6000192.168.0.239
Rack 2
12345678910111213141516171819202122232425Old Sage, 192.168.0.1, A13Old Sage | 192.168.0.1 | A13Backup Main HP Switch, 192.168.0.201, A12, B24Backup Main HP Switch | 192.168.0.201 |...R740, 192.168.3.241, A21, B19R740192.168.3.241 | A21, B19JMFXDATA, 192.168.0.197, A17, B5JMFXDATA192.168.0.197 | A17, B5R740, 192.168.3.226, A1, B9R740192.168.3.226 | A1, B9HP ProLiant, 192.168.0.221, A11, C7HP ProLiant192.168.0.221 | A11, C7JMFXDATA2, 192.168.0.200, A20, C15JMFXDATA2192.168.0.200 | A20, C15Proxmox, 192.168.0.54, D13Proxmox192.168.0.54 | D13R610 (Dave), 192.168.0.84, A7, B1R610 (Dave) | 192.168.0.84 | A7, B1JMFPMX01, 192.168.3.198, A6, C13JMFPMX01192.168.3.198 | A6, C13SRT2200, 192.168.3.252SRT2200192.168.3.252APC UPS, 192.168.0.240APC UPS192.168.0.240
Rack 3
vm-hostserverswitchfirewallnasupsother

Power per rack

Rack 1

1,764W of 4,200W protected

42% of connected UPS capacity, measured. Nameplate 6,110W. Another 1,980W is racked but not yet cabled.

  • SYM-1 Symmetra RM 6000 192.168.0.248 · 42% load, 19 min
  • SRT-1 Smart-UPS SRT 2200 192.168.3.250 · 0% load

Rack 2

1,218W of 4,200W protected

29% of connected UPS capacity, measured. Nameplate 3,280W. Another 1,980W is racked but not yet cabled.

  • SYM-2 Symmetra RM 6000 192.168.0.239 · 29% load, 28 min
  • SRT-2 Smart-UPS SRT 2200 192.168.3.251 · 0% load

Rack 3

2,004W of 0W protected

NO WORKING UPS on this rack, load estimated at 32 percent of nameplate. Nameplate 6,310W. Another 1,980W is racked but not yet cabled.

  • SRT-3 Smart-UPS SRT 2200 192.168.3.252 · 0% load
  • OLD-3 APC (unidentified) 192.168.0.240 · dead, no HTTP and no SNMP response on 2026-09-29, replace with SRT-3

The three SRT2200 units are racked and on the network but carry no load yet: all three report 0 percent. Rack 3 has no Symmetra and its old 0.240 UPS answers nothing on HTTP or SNMP, so rack 3 is the one rack with no measured protection today. Its estimate of about 2,000W exceeds the 1,980W an SRT2200 can carry, which is why its feed is a decision and not a plan.

Proposed feed plan

Not cabled yet. Rows marked decision need a call before anything is plugged in.

RackPrimary feedSecondary feedStatusDetail
Rack 1SRT-1 (3.250) takes PSU A of all five Rack 1 cluster nodes, the firewall and both core switchesSRT-2 (3.251) moves into Rack 1 and takes PSU B of the same setokThis is the whole point of the exercise. Rack 1 holds five of the six cluster nodes (JMFPMX02, 03, 04, 05, 06) and they draw 922W measured, not the 4,350W their nameplate claims. One SRT2200 carries all five at 47 percent, so two of them split across PSUs sit at about 24 percent each and still hold the whole rack at 47 percent if either dies. SYM-1 is then left carrying only the Syn NAS and the ISP handoff, and its habit of dropping to bypass on every transfer stops being able to take the cluster down.
Rack 2SYM-2 (0.239) keeps PDU rail CSRT-3 (3.252) as the second feed for the two R520s and the R710okRack 2 draws 1,218W measured against 4,200W on SYM-2. SYM-2 is the healthier of the two Symmetras, though its last self test returned invalid rather than passed on 09-24.
Rack 3unchanged until it can be measureddecisionRack 3 still cannot be measured: its two PDU rails have no management IP, and its old UPS at 0.240 is dead. Two of its R740s do answer over iDRAC and draw only 90W and 115W, which suggests the rack is far lighter than its 6,310W nameplate implies. Address the PDUs and this stops being a guess.

Wall mounted

DeviceIPRoleWattsPDU outletsNote
Main HP Switch192.168.0.201switch1050C22this IP is the LAN default gateway, so it is the core L3 switch; no SNMP, model unconfirmed
HP Switch192.168.0.147switch630A23
HP Switch192.168.0.208switch630D3
Lobby UbiquitiapD22
Loft UbiquitiapA22
Kitchen UbiquitiapD20
AlarmotherD3
DVR and monitorotherD4

PDU rails

RailIPModelLoadMACLocationNote
Aunknown00:c0:b7:cc:ff:66Rack 3, rightno management IP found, scanned .235 to .255 on 192.168.0 and 192.168.3
Bunknown00:c0:b7:cc:fe:e2Rack 3, leftno management IP found, same scan
C192.168.0.251AP79329.6A00:c0:b7:cc:fd:88Rack 2, rightmeasured 2026-09-29
D192.168.0.253AP79328.6A00:c0:b7:cc:fa:4bRack 1, rightmeasured 2026-09-29

All devices


RackUDeviceIPRoleNameplateMeasuredPDU outletsNote
Rack 1U26HP Switch192.168.0.210switch630D11
Rack 1U25HP Switch192.168.0.212switch630D15
Rack 1U24 to U23JMFPMX02192.168.3.232vm-host700149D24, C21PowerEdge R730, web
Rack 1U22Fiber / ComcastotherD1, D14ISP handoff
Rack 1U21Firewall192.168.0.194firewallD23, C9
Rack 1U20Mini NG SwitchswitchD12
Rack 1U19F FW192.168.0.190firewallD6
Rack 1U18 to U17JMFPMX03192.168.3.199vm-host750188D19, C24PowerEdge R740, hosts JMFDC2 + Exchange
Rack 1U16 to U15JMFPMX04192.168.0.232vm-host750172A14, C16PowerEdge R730
Rack 1U14 to U13JMFPMX06192.168.3.200vm-host750148A19, C2PowerEdge R740, joined 2026-09-21
Rack 1U12 to U11JMFPMX05192.168.3.190vm-host1400265C5, A16PowerEdge R750
Rack 1U10 to U9Syn NAS192.168.0.196nas500C10, D7Synology 1 of 3, replica NAS, PBS DS001 datastore
Rack 1U8 to U7SRT2200192.168.3.250upsSRT-1, no load yet
Rack 1U6 to U1Symmetra RM 6000192.168.0.248upsSYM-1, 42 percent, 19 min
Rack 2U17HP Switch192.168.0.211switch630C20
Rack 2U16 to U15R520 VM192.168.3.196server750B7, A24
Rack 2U14 to U13R520 VM192.168.0.222server750D17, C19
Rack 2U12 to U11Storage192.168.0.220nas550A8, B10POWERED OFF, no ping 2026-09-29
Rack 2U10 to U9R710 VM192.168.0.227server600A18, C11
Rack 2U8 to U7SRT2200192.168.3.251upsSRT-2, no load yet
Rack 2U6 to U1Symmetra RM 6000192.168.0.239upsSYM-2, 29 percent, 28 min
Rack 3U25Old Sage192.168.0.1serverA13pings and answers HTTP 401, no SNMP; Greg knows of nothing running here
Rack 3U24Backup Main HP Switch192.168.0.201switch460A12, B24
Rack 3U23 to U22R740192.168.3.241server110090A21, B19
Rack 3U21 to U20JMFXDATA192.168.0.197nas550A17, B5Synology 2 of 3, office NAS, git origin
Rack 3U19 to U18R740192.168.3.226server750115A1, B9
Rack 3U17 to U16HP ProLiant192.168.0.221server400A11, C7POWERED OFF, confirmed by Greg
Rack 3U15 to U14JMFXDATA2192.168.0.200nas500A20, C15Synology 3 of 3
Rack 3U13 to U12Proxmox192.168.0.54vm-host750D13
Rack 3U11R610 (Dave)192.168.0.84server700A7, B1POWERED OFF, no ping 2026-09-29
Rack 3U10 to U9JMFPMX01192.168.3.198vm-host1100213A6, C13PowerEdge R740, hosts JMFDC
Rack 3U8 to U7SRT2200192.168.3.252upsSRT-3, no load yet
Rack 3U6 to U1APC UPS192.168.0.240upsdead, no HTTP and no SNMP, replace with SRT-3